Analisis Efektivitas Cooling Tower Sebelum dan Sesudah Pergantian Filler Pack
DOI:
https://doi.org/10.37859/jst.v11i1.7326
Abstract
Cooling towers are components used to lower the temperature of condensate water from the condenser, which is pumped through the hot well pump. Given the importance of cooling towers as components used to lower condensate water temperature, the performance of these cooling towers must be maintained. One way to determine the effect of the filler pack is to conduct an analysis to determine the effectiveness parameters of the cooling tower. The analysis was conducted using the range approach and heat transfer methods. The results showed that the heat transfer effectiveness before replacing the filler pack was 68%, while after the replacement, the effectiveness increased to 72%. This indicates that replacing the filler pack has succeeded in increasing the effectiveness of the cooling tower.
Downloads
References
Ahluriza, P., Sinaga, N. Review Pengaruh Range dan Approach terhadap efektivitas Cooling Tower di PT. IP. Jurnal Pendidikan Teknik Mesin Undiksha. 2021, Vol 9(2): 134-142.
Fikri, M. I., Wuryanti, S., & Kurniasetiawati, A. S. Perancangan Variasi Bentuk Filler pada Menara Pendingin Tipe Induced Draft Counterflow di PT Indolakto–Jakarta. In Prosiding Industrial Research Workshop and National Seminar. 2022; vol 13:837-842.
Handoyo, Y. Analisis Performa Cooling Tower LCT 400 Pada PT XYZ. Jurnal Ilmiah Teknik Mesin. 2015, Vol 3:hal38-52.
Hensley, J. C. Cooling tower fundamentals. Kansas City: Marley Cooling Tower Company. 1985
Wuryanti, Sri. Mekanisme Perpindahan Panas. Yogyakarta: DEEPUBLISH. 2002.
Muhsin, A., & Pratama, Z. (2018). Analisis Efektivitas Mesin Cooling Tower Menggunakan Range and Approach. Opsi, 11(2), 119-124.