Evaluasi Uprating Transformator Distribusi 20 KV pada Penyulang Kelinci di PT. PLN (Persero) ULP Rumbai
DOI:
https://doi.org/10.37859/jst.v11i2.7907
Abstract
The need for electrical energy affects the loading of the transformer which can result in overloading of more than 80%. PLN Standard No. 50 of 1997 states that a transformer is said to be overloaded if the load is more than 80%. This research aims to determine the effect of loading on transformer efficiency and voltage drop on distribution transformers. For loading on transformers before uprating, the results were 92.143%. The voltage drop percentage value obtained for each phase R, S, T is 11.121%, voltage drop percentage on the R phase, 10.973% voltage drop percentage on the S phase, 10.167% voltage drop percentage on the T phase. Uprating was carried out on the transformer to reduce overloading. After the uprating was carried out, the loading results were 55.568 % , which was in accordance with the permitted loading standards. The voltage drop percentage value obtained for each phase R, S, T is 10.973%, voltage drop percentage on the R phase, 10.524 % voltage drop percentage on the S phase, 9.637 % voltage drop percentage on the T phase.
Downloads
References
SPLN No. 50. (1997). Spesifikasi Transformator Distribusi. P.T Perusahaan Listrik Negara.
Soebagio. (2012). Transformator. ITS Press. Surabaya
Yasa, I. W. S., Pacane, I. W. D., & Suriana, I. W. (2023). Mengatasi Overload Pada Transformator Gardu Distribusi Dengan Metode Uprating. Kajian Teknik Elektro, 8(2), 82–91.
Samsurizal, & Hadinoto, B. (2020). Studi Analisis Dampak Overload Transformator Terhadap Kualitas Daya Di PT. PLN(Persero) Up3 Pondok Gede. Kilat, 9(1), 136–142. https://doi.org/10.33322/kilat.v9i1.784
Muchtar, H., & Sopian, Y. (2017). Studi Verifikasi Sistem Ketidakseimbangan Beban Pada Jaringan Tegangan Rendah Menggunakan Alat Phb – Sr (Peralatan Hubung Bagi Sambungan Rumah) Di Wilayah Pln Area Cempaka Putih. Elektum, 14(1). https://doi.org/10.24853/elektum.14.1.1-8