Abstract

The grounding system for the 20 kV switchgear at the Bukit Asam Tanjung Enim town site housing complex (capacity 591,147 kW) plays a crucial role in protecting equipment and personnel from overcurrent faults and touch voltage. This study aims to evaluate the existing conditions, compliance with the PUIL 2020 and IEEE Std 80-2013 standards, factors affecting resistance, and recommendations for improvements. Methods included direct measurements using an ETCR 2100A+ clamp meter, theoretical calculations using the Dwight formula (ρ = 30–35 Ωm), and a comparative analysis of pre- and post-maintenance conditions. The results show that the resistance after maintenance was 0.17–0.91 Ω (average 0.42 Ω), down from 0.91 Ω before maintenance. Theoretical calculations yielded 4.77 Ω (ρ = 30 Ωm). All values were below the maximum limit of 5 Ω, so the system was deemed serviceable and safe. Factors affecting resistance include the condition of the connections, corrosion, soil moisture, and soil resistivity. Routine maintenance proved effective in significantly reducing resistance.

Downloads

Download data is not yet available.

Author Biographies

Yogi Edi Pratama, Universitas Palembang

Program Studi Teknik Elektro, Fakultas Teknik

Dian Eka Putra, Universitas Palembang

Program Studi Teknik Elektro, Fakultas Teknik

Raden Ahmad Yani, Universitas Palembang

Program Studi Teknik Elektro, Fakultas Teknik

References

M. R. Aprianto, D. E. Putra, R. A. Yani, and C. Rizal, “Evaluation of the Coordination of the 250 kVA Distribution Transformer Protection System Between Lightning Arrester and Grounding System,” J. Renew. Energy, Electr. Comput. Eng., vol. 6, no. 1, pp. 35–40, 2026, doi: https://doi.org/10.29103/jreece.v6i1.24242.

T. M. Sari, D. E. Putra, and R. A. Yani, “Metode Penurunan Resistansi Pentanahan Arrester pada Gardu Distribusi untuk Meminimalisir Terjadinya Ground Potential Rise ( GPR ),” J. Surya Tek., vol. 13, no. 1, pp. 142–149, 2026, doi: 10.37859/jst.v13i1.11219.

R. A. Yani, D. E. Putra, R. M. E. Suherman, and J. Ardian, “Penggunaan Arrester Sebagai Pengaman Gardu Distribusi 20 KV Pada Trasformator 160 KVA di Penyulang Akasia,” AMPERE, vol. 9, no. 2, pp. 141–149, 2024, doi: http://doi.org/10.31851/ampere.

M. Y. Syam and N. Zahra, “Pengukuran Nilai Resistivitas Tanah pada Transformator Distribusi di Wilayah Makassar,” Arus J. Sains dan Teknol., vol. 2, no. 2, pp. 234–239, 2024, doi: 10.57250/ajst.v2i2.592.

IEEE Std 80, Guía IEEE para la seguridad en la conexión a tierra de subestaciones de CA. Norma IEEE 80-2013 (revisión de la norma IEEE 80-2000/incorpora la norma IEEE 80-2013/Cor 1-2015). 2015.

BSN, “Persyaratan Umum Instalasi Listrik 2020 (PUIL 2020),” DirJen Ketenagalistrikan, vol. 2020, no. PUIL, pp. 1–850, 2020.

Junaidi, D. E. Putra, and C. Rizal, “Tinjauan Perbandingan Resistansi Pentanahan antara Perencanaan dan Hasil Uji Komisioning Di Gardu Distribusi 20 kV,” J. Ampere, vol. 9, no. 1, pp. 18–24, 2024, doi: http://doi.org/10.31851/ampere.

D. E. Putra, Y. Randika, I. Randika, and H. Inamullah, “Enhancing grounding system efficiency through biopore technique in seasonal soil conditions,” Int. J. Adv. Technol. Eng. Explor., vol. 11, no. 113, 2024, doi: http://dx.doi.org/10.19101/IJATEE.2023.10102391.

N. Permal, M. Osman, M. Z. A. A. Kadir, and A. M. Ariffin, “Review of Substation Grounding System Behavior under High Frequency and Transient Faults in Uniform Soil,” IEEE Access, vol. 8, pp. 142468–142482, 2020, doi: 10.1109/ACCESS.2020.3013657.

D. Pranatali, G. Gunawan, and D. Nugroho, “Analisa Kelayakan Pentanahan Tower Saluran Udara Tegangan Tinggi (SUTT) 150kV Jelok – Bringin Menggunakan Metode Komparasi,” JTEV (Jurnal Tek. Elektro dan Vokasional), vol. 8, no. 2, p. 370, 2022, doi: 10.24036/jtev.v8i2.114321.

B. E. Prasetyo, A. Hermawan, and S. Azizah, “Analisis Perbaikan Sistem Pentanahan Tower 70 kV pada Transmisi Wlingi - Blitar,” Elposys J. Sist. Kelistrikan, vol. 9, no. 3, pp. 205–209, 2023, doi: 10.33795/elposys.v9i3.970.

Rahmawati Fajri Latiefa, Irzan Zakir, and Massus Subekti, “Pengaruh Kelembaban Tanah Terhadap Tahanan Pentanahan Studi Kasus Pada Gardu Induk Kemayoran 150 Kv,” J. Electr. Vocat. Educ. Technol., vol. 6, no. 1, pp. 44–49, 2021, doi: 10.21009/jevet.0061.09.

Published

2026-06-30

How to Cite

[1]
Y. E. Pratama, D. E. Putra, and R. A. Yani, “Evaluasi Sistem Pentanahan Kubikel 20 kV Berdasarkan Standar PUIL 2020 dan IEEE Std 80-2013”, JST, vol. 13, no. 1, Jun. 2026.

Issue

Section

Research Article